Rosslare AC-215 Manuale di Installazione Pagina 22

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 38
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 21
Input and Output Connections
22 AC-215IP Hardware Installation Manual
Figure 11: Normally Open Supervised Input (Single Resistor)
4.1.4 Normally Open Supervised Double Resistor Input Connection
Connect a resistor of 2.2 K in series to the input switch contacts.
Connect a resistor of 8.2 K parallel to the input switch contacts.
Normally Open Supervised Input has 3 states:
Switch OpenNormal State:
Loop resistance = 10.4 K
Switch Closed Abnormal State:
Loop resistance = 2.2 K
Open circuit (infinite loop resistance) or short circuit (0 resistance) across
input terminalsTrouble State
Figure 12: Normally Open Supervised Input (Double Resistor)
Vedere la pagina 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 37 38

Commenti su questo manuale

Nessun commento